A contractor in Dammam called me about a batch of 800 mm spiral duct that the flange fitter could not assemble. The flanges were correct. The duct was correct on paper. But when the ring was slipped over the end, it went on at the top and jammed at the bottom. The customer measured the pipe in the truck: 801 mm one way, 807 mm the other. Six millimetres of ovality, and the whole batch needed re-rounding before it could ship.
Ovality — out-of-roundness — is one of those defects that looks harmless on the shop floor and becomes expensive the moment the duct meets a fitting. I have seen it blamed on the flange supplier, on the transport, and on the weather. It is almost always made on the forming line, and once you know where to look, it is usually easy to fix.
This article is about what causes ovality in spiral duct, how to measure it honestly, what limits are realistic by diameter, and how to correct it without slowing the line to a crawl. I am writing from the point of view of someone who has stood at the tubeformer with a tape measure and a dial gauge more times than I care to count.
Ovality is simply the difference between the largest and smallest outside diameter measured in the same cross-section. A duct that measures 800.0 mm in one direction and 803.5 mm ninety degrees around has 3.5 mm of ovality. Note that the average might still be exactly 800 mm, so a single diameter check with a tape can pass a section that will not accept its flange.
It matters for three reasons. Flanges and couplings are round; an oval pipe either will not fit or fits with a gap that leaks. The gasket seating on a spiral duct joint relies on even contact, and an oval section compresses the gasket on two sides and leaves it loose on the others. And the stiffness of the finished duct drops sharply as ovality increases — an oval tube buckles under external pressure at a lower load than a round one of the same wall thickness, which matters on high-rise and buried applications.
People obsess over hitting the nominal diameter and ignore shape. On a spiral line the diameter is largely set by the forming head and is fairly stable. The shape is what drifts.
Four causes account for nearly every case I have investigated. They produce slightly different patterns, which is useful because the pattern tells you which one you have.
The spiral tubeformer wraps strip around a mandrel at a fixed helix angle. If the strip feed is not square to the forming head, or if the angle drifts as the coil tension changes, the strip tries to follow a slightly different helix and the tube comes out with a regular oval pattern along its length. This is the most common cause on a well-maintained machine, and it often shows up only when a new coil supplier changes the strip's springback.
The internal mandrel and the external forming rolls set the diameter. If the mandrel is worn on one side, or the guide rolls are not symmetric about the tube axis, the section becomes oval in a consistent direction — the same side of every pipe is the long side. Walk along a stack and if the ovality always points the same way relative to the seam, suspect the tooling geometry rather than the feed.
A coil that has been stored tightly for months wants to stay curled. As it feeds, that memory adds a bending moment that the forming head has to overcome, and the result is a tube with a gentle ellipse. Material with high springback — stainless, some aluminium tempers, and heavily work-hardened galvanised strip — is worse. Coil storage and handling matter here as much as the machine settings.
Not all ovality is formed at the head. A plasma cut that starts with the torch slightly off-centre can leave a burr that the cut-off clamp deforms. More commonly, long sections are supported badly after the cut: a four-metre pipe picked up by two slings at the ends will sag in the middle and take a permanent oval set, especially in thin wall. I have seen perfectly round duct leave the machine and arrive oval at the other end of the shop because a forklift driver carried two lengths side by side on the forks.
| Symptom | Likely cause | First check | Typical fix |
|---|---|---|---|
| Ovality varies along the length, no fixed direction | Strip feed / helix angle | Strip squareness at entry | Realign feed guides, check coil tension |
| Same side always long, every section | Mandrel or roll asymmetry | Measure roll gaps top and bottom | Re-centre rolls, replace worn mandrel |
| Worse after coil change, improves as coil unwinds | Coil memory / springback | Compare first and last 20 m | Adjust decoiler brake, add levelling pass |
| Round at machine, oval at stacking area | Handling / support | Measure before and after lifting | Add cradles, lift at two points with spreader |
| Oval concentrated near the cut end only | Cut-off clamp or torch | Inspect clamp pads and torch alignment | Soften clamp, centre torch, reduce cut force |
The honest method is a diameter tape around the outside at several points along the section, or a pair of callipers measuring two perpendicular diameters at the same station. A diameter tape is quicker and less dependent on the operator's feel, but it needs to be pulled evenly — too tight and it flattens a thin wall, too loose and it reads high.
Measure at the two ends and at the middle. Then rotate the tape ninety degrees and measure again. For a 4 m section I take readings at 0.2 m, 2 m and 3.8 m from one end, two directions each. That is six numbers and it takes under two minutes. If the two ends are round and the middle is oval, the problem is handling or support. If all three stations are oval in the same direction, the problem is at the head.
Record the direction of the long axis, not only the magnitude. A note like "4 mm, long axis 2 o'clock" is infinitely more useful than "4 mm out" because it points to the offending roll or guide. On one job in Ho Chi Minh City, that simple notation isolated a worn lower guide roll in about ten minutes after two days of general adjusting.
For thin wall duct, a rigid internal gauge is better than an external tape because it does not deform the section. A simple expanding disc gauge made in the shop is adequate; it does not need to be a calibrated instrument for shop-floor control, though the master should be checked periodically against a known ring.
Standards and project specifications vary, so treat the figures below as the working limits I use for commercial galvanised spiral duct rather than as contractual values. Wall thickness matters: thin wall is less able to resist ovality and harder to correct.
| Diameter | Wall (galv.) | Good practice | Action limit | Reject |
|---|---|---|---|---|
| 200–315 mm | 0.7–0.8 mm | ≤ 1.5 mm | 2–3 mm | > 4 mm |
| 355–500 mm | 0.8–1.0 mm | ≤ 2.0 mm | 3–4 mm | > 5 mm |
| 560–800 mm | 1.0–1.2 mm | ≤ 3.0 mm | 4–6 mm | > 8 mm |
| 900–1200 mm | 1.2–1.5 mm | ≤ 4.0 mm | 6–8 mm | > 10 mm |
Below the action limit the duct is usable and usually rounds out as the flange is tightened. Between the action limit and reject, re-round before assembly. Above the reject line, scrap or send back for re-forming — trying to salvage a badly oval large duct costs more in labour than the material is worth, and it will still leak.
Stainless and aluminium need slightly tighter limits because they spring back further after re-rounding. Add roughly one millimetre of tolerance to the good-practice column if you are forming 0.8 mm stainless; the elastic recovery after a correction pass will otherwise undo your work.
Start with the cheapest adjustment, which is usually strip tension. If the brake on the decoiler is too tight, the strip is being stretched as it enters the head and the resulting ovality follows the coil memory. Relax it until the strip feeds with a slight, controlled drag. Too loose is also bad — the strip wanders and the seam becomes inconsistent — so make small changes and measure after each one.
Next, check the forming roll gaps on both sides of the tube. On a machine such as the fixed-head spiral tubeformer, the rolls are adjustable and should be symmetric. A difference of even half a millimetre between top and bottom can produce two millimetres of ovality on a 600 mm section. Set them with the same feeler gauge and write the values on the machine.
If the mandrel is suspect, measure it at several points around its circumference. Wear is rarely even, and a mandrel that has seen a few thousand metres of abrasive galvanised strip can be noticeably oval itself. A worn mandrel cannot be adjusted away; it has to be replaced or refurbished. This is where an accurate machine pays back its price — the rigidity holds the geometry under load, and you spend less time chasing shape.
Do not overlook the cut-off. A clamp that closes too hard on a thin tube squeezes it oval right at the end, which is exactly where the flange goes. Pad the jaws with a soft material, reduce the closing pressure, and check the first section after the cut rather than only the running tube. The seam welding station has a similar effect: excessive pressure from the weld rolls can flatten the tube locally. If the ovality follows the seam line, look at the roll pressure on the welding station before you touch the forming head.
For sections that are already made and slightly out of shape, a re-rounding stand is worth having. The shop version is a rigid circular former with a screw jack and a set of adjustable shoes; push the oval section through it or expand it internally, working gradually around the circumference. Do not try to correct six millimetres in one pass. Take out two, rotate, take out another two.
Beading stiffens the wall and reduces the chance of the section going oval again during handling, but it will not fix existing ovality — it locks in whatever shape the duct has at the moment the bead is formed. That means the sequence matters: re-round first, then bead. If the beading operation itself is introducing distortion, check that the beading rolls are not pressing too hard against a thin wall, particularly at the seam where the material is already work-hardened.
After re-rounding, re-measure. I have seen shops spend an hour correcting a section and then load it straight onto a truck without a single confirming measurement. Six numbers and two minutes, every time.
First, measure the first section of every coil and write the ovality next to the coil number. When a new coil arrives with different springback, you will see the change immediately instead of discovering it in a rejected batch. This takes the guesswork out of the "did the material change?" question that comes up in every investigation.
Second, support long duct properly between the machine and the stack. A simple cradle every two metres costs almost nothing and prevents more ovality than any setting change. Use a spreader beam when lifting, and never drag a section off the outfeed table by one end. The money spent on a few cradles is usually recovered in the first week through avoided rework.
For shops comparing forming routes, the technical guides section explains how spiral and rectangular lines differ in their tolerance behaviour. Whichever route you run, the principle is the same: measure shape, not just size, and record the direction of the error.
For commercial galvanised work I treat 3 mm as good practice and 6 mm as the point where re-rounding is needed, with 8 mm as reject. Check the project specification first — some data centre and cleanroom jobs are stricter. Measure two directions at three stations along the section, because a single tape reading can pass a pipe that will not accept its flange.
Up to about the action limit it can be re-rounded on a simple shop stand, provided the seam is sound. Work gradually and re-measure after each pass. Above the reject line, or if the seam splits during correction, the labour costs more than the section. On large diameters, re-forming the material is usually the cheaper route.
Yes. An oval tube is less resistant to external pressure and buckles earlier than a round one of the same wall. It also reduces gasket contact at flanged joints, which raises leakage. On a system that is pressure-tested or runs under negative pressure, ovality is a structural issue, not a cosmetic one.
At the start of every shift, after every coil change, and whenever the forming rolls are adjusted. That is three situations, not a continuous inspection regime. Six readings take two minutes and give you a record that shows exactly when the shape started to drift.